Customization: | Available |
---|---|
Type: | Gas Alarm Controller |
Usage: | Factory |
Still deciding? Get samples of US$ 1000/Set
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Measurement range | %LEL, %VOL, PPM |
Accuracy | ±3%FS; |
Sensor model | 4-20MA or RS485 |
Alarm point | Two-level alarm, can be freely set by the user |
Default value | (EX) Low report: 20%LEL High report: 50%LEL |
Indication mode | LED digital display concentration data, LED indication alarm or fault status |
Output mode | switch, MAX 3.0A |
Working method | On-site fixed installation, wall-mounted |
Network capacity | 3 channels, 4 channels, 5 channels, 6 channels, 7 channels, 8 channels |
Working environment | temperature -20 - 50ºC humidity < 95%RH |
Working voltage | AC220V±l0% 50HZ |
Power | Monitor Max 6W Sensor Max 1W |
Implementation standard | GB16808-2008 |
Overall dimensions | length*width*thickness (cm); 35.5*25*10 (including hanging board) |
Requirements for connecting the system to the external (gas) detector | Standard bus 2-wire connection method, 2 single-core wires with diameter ≥ 2.5mm and line length ≤ 1000m;Standard 3-wire connection method, 3 single-core wires with diameter ≥1.5mm and length ≤1000m;Standard bus 4-wire connection method, 4 single-core wires with diameter ≥1.5mm and line length ≤1000m |